Page 64 • DRI-STEEM GTS Humidifier Installation, Operation, and Maintenance Manual
mc_052908_0815-2
• When the maintenance requirements are complete:
– Replace cleanout plate and tighten the nuts on the plate.
Torque the nuts to 25 to 35 in-lb (2.8 to 4.0 N-m).
– Verify that the probe rod holder is secure and that the
probe plug and cable assembly are plugged into the probe
rod holder.
– Verify that the drain valve assembly is in the closed
position.
– Replace and secure all covers and doors.
– Turn on the water supply.
– Turn on the electrical power.
– Turn on gas.
– Do not leave humidifier unattended. Allow the humidifier
to cycle through multiple fill cycles and verify that the
humidifier cover, cleanout plate, and probe holder gasket
are not leaking.
3. Off-season maintenance
• Perform complete inspection and cleaning of the following:
– Probe rods
– Skimmer port and water seal
– Humidifier tank
– Heat exchanger
• After cleaning, the humidifier should remain empty until
humidification is required.
M a i n t e n a n c e : G T S s t a n d a r d w a t e r
m o d e l s ( c o n t i n u e d )
Maintenance