DRI-STEEM GTS Humidifier Installation, Operation, and Maintenance Manual Page 43
Duct
GTS humidifier
½" (DN15) O.D. condensate
drain tube, pitch ¼"/ft (2%)
Condensate drain tube provided by installer,
¾" (DN20) minimum
Water seal
5" (127 mm)
90° long sweep or
two 45° elbows
6"
(152 mm)
1" (25 mm)
air gap
¼" (DN8)
pipe thread
OM-1215a
Mounting
nut, 3/8"
(M10)
Pitch tube toward drain
1/8"/ft (1%)
Vapor hose, tubing,
or pipe
Figure 43-1:
Multiple tubes with condensate wasted to floor drain
D i s p e r s i o n : S i n g l e t u b e a n d
m u l t i p l e t u b e ( c o n t i n u e d )
Pitch
Pitch
Maximum capacity of dispersion tube:
1½" dia. (DN40): 56.8 lbs/hr (25.8 kg/h)
2" dia. (DN50): 85.2 lbs/hr (38.6 kg/h)
Secure and seal
escutcheon plates
Open drain required.
Locate air gap only in spaces with adequate
temperature and air movement to absorb flash
steam, or condensing on nearby surfaces may
occur. Refer to governing codes for drain pipe
size and maximum discharge water temperature.
Dispersion tube
Notes:
1 Assemble multiple dispersion tubes or use a Rapid-sorb or Ultra-sorb dispersion
assembly where necessary to accommodate maximum humidifier load.
2 The smallest GTS humidifier steam outlet is 2" (DN50). Install an adaptor manifold
if using multiple 1½" (DN40) dispersion tubes. See also Table 37-1.
3 Pitch vapor hose, tubing or pipe toward humidifier:
– 2"/ft (15%) when using vapor hose
– ½"/ft (5%) when using 1½" (DN40) tubing or pipe
– ¼"/ft (2%) when using 2" (DN50) tubing or pipe
4 Dashed lines indicate provided by installer
Pitch (See Notes)
Installation