DRI-STEEM GTS Humidifier Installation, Operation, and Maintenance Manual • Page 27
G a s p i p i n g ( c o n t i n u e d )
“Installation Code for Natural Gas Burning Appliances and
Equipment,” or CAN/CGA-B149.2, “Installation Code for
Propane Burning Appliances and Equipment.”
In Europe: The National Gas Safety (Installation & Use)
Regulations.
• Do not use flexible connectors.
• Piping to units should conform with local and national
requirements for type, volume, and gas handled and for pressure
drop allowed in the line. Refer to the tables on this page to
determine the gas flow in ft
3
/hr or m
3
/hr for the type of gas and
size of unit to install. Using this value and the length of pipe
necessary, determine the pipe diameter. Where several units are
served by the same main, the total capacity, gas flow, and length
of main must be considered. Avoid pipe sizes smaller than ½"
(DN15). Table 27-2 below allows for the usual number of
fittings with a 0.3" wc (0.07 kPa) pressure drop.
• When the specific gravity of the gas is other than 0.60 for natural
gas or 1.53 for propane, use Table 27-1.
Table 27-2:
Gas pipe capacities for gas pressures of 0.5 psig (3.45 kPa) or less
Length
of pipe
Gas flow in piping in ft
3
/hr and m
3
/hr at
pressure drop of 0.3" wc (0.07 kPa)
Specific gravity = 0.60
Nominal iron pipe diameter in inches (DN)
½" (DN15) ¾" (DN20) 1" (DN25) 1¼" (DN32) 1½" (DN40)
ft m ft
3
/hr m
3
/hr ft
3
/hr m
3
/hr ft
3
/hr m
3
/hr ft
3
/hr m
3
/hr ft
3
/hr m
3
/hr
10 3 132 3.7 278 7.9 520 14.7 1050 29.7 1600 45.3
20 6 92 2.6 190 5.4 350 9.9 730 20.7 1100 31.1
30 9 73 2.1 152 4.3 285 8.1 590 16.7 890 25.2
40 12 63 1.8 130 3.7 245 6.9 500 14.2 760 21.5
50 15 56 1.6 115 3.3 215 6.1 440 12.5 670 19.0
60 18 50 1.4 105 3.0 195 5.5 400 11.3 610 17.3
70 21 46 1.3 96 2.7 180 5.1 370 10.5 560 15.9
80 24 43 1.2 90 2.5 170 4.8 350 9.9 530 15.0
90 27 40 1.1 84 2.4 160 4.5 320 9.1 490 13.9
100 30 38 1.1 79 2.2 150 4.2 305 8.6 460 13.0
See example on page 28.
Table 27-1:
Specific gravity conversion factors
Natural gas
Specific gravity Factor
0.55 1.04
0.60 1.00
0.65 0.962
Propane gas
Specific gravity Factor
1.50 0.633
1.53 0.626
1.60 0.612
Note:
Use the above multiplying factor with Table: 27-2
when the specific gravity of gas is other than 0.60
(natural gas) or 1.53 (propane).
More gas piping instructions
on the next page ▶