Page 62 • DRI-STEEM GTS Humidifier Installation, Operation, and Maintenance Manual
Inspection and maintenance
1. Annually (also recommended when maintenance is performed)
• Inspect tank, piping, and gaskets for water and gas leaks.
• All safety devices in the control circuit should be cycled on
and off to verify they are functioning. These include:
– High limit switch
– Airflow proving switch
– Low water level probe. Pull out probe plug; fill valve should
energize.
– Redundant low water level probe
2. Seasonally (or as required, depending on water quality)
• Clean tank
– Remove cleanout plate and dispose of any loose scale that
has collected in the tank. Do this before the scale buildup
reaches the bottom of the heat exchanger.
– Inspect the area inside the tank in front of the drain valve
fitting and thoroughly clean all scale and mineral buildup
from that area.
• Dismantle and clean drain valve and associated piping
• Clean the probes
– Access the probe assembly either from the electrical panel
or by removing the roof panel above the electrical area.
– Disconnect the probe plug and cable assembly and unscrew
the probe rod assembly from the humidifier probe housing.
– Inspect the probe housing and clean, ensuring that all the
housing passageways are clear. Remove the housing from
the tank by removing the cover plate from the tank.
– The scale should flake off easily from the probe assembly
rods.
– The bottom 3/8" (10 mm) of each rod is the sensing
portion; clean these areas with a wire brush, abrasive pad,
or steel wool.
– Inspect the composite plastic probe rod assembly for any
signs of cracking, roughness, or deterioration. If found,
replace probe assembly.
– Reassemble the probe assembly.
mc_052908_0815-1
M a i n t e n a n c e : G T S s t a n d a r d w a t e r
m o d e l s ( c o n t i n u e d )
More on next page ▶