DRI-STEEM GTS Humidifier Installation, Operation, and Maintenance Manual Page 55
Safety systems
The GTS humidifier has a number of systems and safeguards to
ensure proper operation.
• When there is a call for humidity, all of the combustion blowers
must start. Each combustion blower sends a signal to the
microprocessor relaying its current speed. If this actual speed is
outside an acceptable range, the GTS will not operate.
• The negative pressure gas valves used on the GTS are designed
to keep a constant ratio of air and gas throughout the operating
range of the blower. If the flue becomes blocked or the
blower fails to run, the blocked flue sensor will shut down the
humidifier.
• During operation, the water level in the tank is monitored by a
probe system for standard water units and by a low water float
for DI/RO units. These water monitors tie into the Vapor-logic4
controller. If the water level drops below a safe point, the
controller turns heaters off and tries to fill. If humidifier is unable
to fill within a defined time period, an “Excessive refill time”
alarm appears in the Vapor-logic4 Alarm Log. The heaters will
remain off until this alarm is cleared. (For more about alarms, see
the Vapor-logic4 Installation and Operation Manual.)
• In standard water applications, the water level in the tank is
also monitored by a redundant low-water system that runs
independently of the Vapor-logic4. This system is tied directly
into the power source for the gas valves. If this system detects
a low water condition, the humidifier shuts down until water is
present or until the a “GTS low water” alarm is cleared from the
Vapor-logic4 Alarm Log.
• In addition to monitoring the water level, there is a temperature
sensor located near the top of the heat exchanger. If the water
level drops too low and both the main and redundant low water
sensors fail to detect it, the temperature sensor shuts down the
humidifier before an unsafe condition occurs.
O p e r a t i o n : S a f e t y s y s t e m s