Page 58 DRI-STEEM GTS Humidifier Installation, Operation, and Maintenance Manual
mc_052708_1555
mc_051408_1430
M a i n t e n a n c e : G T S a n d G T S - D I m o d e l s
Both GTS and GTS-DI models
Inspection recommendations:
• User inspection every 30 days.
• Appliance system inspected once a year by a qualified service
person.
During inspection, verify the following:
• Proper field operation of burner. Measure CO, CO
2
%, O
2
%, flue
temperature, and burner efficiency at 100% demand with the
tank at a boil. Verify that measurements are within the guidelines
described in Table 58-1; if not, consult DRI-STEEM.
• Flue passageways external to the appliance, such as vent
connector and chimney, are clear and free of obstructions.
• Vent connector is in place, sloping upward and is physically
sound without holes or excessive corrosion.
• Physical support of the appliance is sound without sagging,
cracks, or gaps between floor stand or tank flanges.
• There are no obvious signs of deterioration of the appliance.
• Burner flame is blue or orange in color — up to a ¼"
(6 mm) from the surface of the burner.
• See “Clean the probes” and “Clean low water cutout probe” on
Page 62 and 63.
Inspecting burner assemblies and heat exchanger tubes
This is not a regular maintenance item, but if the heat exchanger
tubes contain carbon deposits, soot, or other residue, clean as
follows:
• Turn off gas, electrical power, and water supply.
• Remove gas train shroud.
• Disconnect wiring to blowers, flame sensors, gas valves, and
ignition controllers and remove burner assemblies (each assembly
is mounted with four bolts).
• Remove vent box.
• Use a 6" (150 mm) flue brush with a 24" (600 mm) extension
and reversible drill. Work brush in and out of all combustion
chambers. Note: Disconnecting components from one burner
assembly at a time and then cleaning the corresponding
combustion chamber and burner will ease reassembly.
More on next page
Table 58-1:
GTS products of combustion guidelines
(at 100% demand)
CO
Less than 40 ppm; 0 or low single
digits is typical
CO
2
%
8-10%; 9% is typical for natural gas,
10% is typical for LP gas
O
2
% 4-7%
Flue
temperature
Less than 400 °F plus room temp.
(Less than 204.4 °C plus room temp.)
Burner
efficiency
Greater than 80%
mc_052708_1610
Maintenance