Page 20 DRI-STEEM GTS Humidifier Installation, Operation, and Maintenance Manual
G T S p i p i n g , s t a n d a r d w a t e r m o d e l s
Figure 20-1:
Field piping overview for GTS standard water models
Table 20-1:
Height required to overcome GTS internal pressure (H)
GTS model
number
H = Height required to overcome humidifier internal pressure
inches mm
100, 200 35 889
300, 400,
500, 600,
700, 800
41 1041
Notes:
Locate air gap only in spaces with adequate
temperature and air movement to absorb flash steam;
otherwise, condensation may form on nearby surfaces.
Refer to governing codes for drain pipe size and
maximum discharge water temperature.
Dashed lines indicate provided by installer.
Humidifier flue gases must be vented to the outside
atmosphere.
The water supply inlet is more than 1" (25 mm) above
the skim/overflow port, eliminating the possibility of
backflow or siphoning from the tank. No additional
backflow prevention is required; however, governing
codes prevail.
Damage caused by chloride corrosion is not covered by
your DRI-STEEM warranty.
See the next page for recommended water supply
piping for DI/RO water models.
OM-1208
Flue size per governing codes.
Do not reduce.
Water supply line; water
pressure range 25 psi to 80 psi
(172 kPa to 582 kPa); water
conductivity minimum 100 µS/cm
Shock arrester recommended to
reduce water hammer, by installer
Flue connection
Gas inlet connection
1" (25 mm) air gap
Open drain required.
See first note below.
1½" NPT (DN40) drain piping must be
rated for 212 °F (100 °C) (by installer)
Install level
Optional condensate return piping from dispersion
unit; ¾" pipe thread (DN20) fitting at humidifier
Air vent height must be equal to
or greater than dimension “H”
(see table below)
Steam hose, pipe or tubing
H
Offset humidifier from floor
drain to prevent flash steam
from rising into the humidifier
Air vent tube
6" (150 mm)
minimum vent height
Install level
Installation