Page 20 • DRI-STEEM GTS Humidifier Installation, Operation, and Maintenance Manual
G T S p i p i n g , s t a n d a r d w a t e r m o d e l s
Figure 20-1:
Field piping overview for GTS standard water models
Table 20-1:
Height required to overcome GTS internal pressure (H)
GTS model
number
H = Height required to overcome humidifier internal pressure
inches mm
100, 200 35 889
300, 400,
500, 600,
700, 800
41 1041
Notes:
• Locate air gap only in spaces with adequate
temperature and air movement to absorb flash steam;
otherwise, condensation may form on nearby surfaces.
Refer to governing codes for drain pipe size and
maximum discharge water temperature.
• Dashed lines indicate provided by installer.
• Humidifier flue gases must be vented to the outside
atmosphere.
• The water supply inlet is more than 1" (25 mm) above
the skim/overflow port, eliminating the possibility of
backflow or siphoning from the tank. No additional
backflow prevention is required; however, governing
codes prevail.
• Damage caused by chloride corrosion is not covered by
your DRI-STEEM warranty.
• See the next page for recommended water supply
piping for DI/RO water models.
OM-1208
Flue size per governing codes.
Do not reduce.
Water supply line; water
pressure range 25 psi to 80 psi
(172 kPa to 582 kPa); water
conductivity minimum 100 µS/cm
Shock arrester recommended to
reduce water hammer, by installer
Flue connection
Gas inlet connection
1" (25 mm) air gap
Open drain required.
See first note below.
1½" NPT (DN40) drain piping must be
rated for 212 °F (100 °C) (by installer)
Install level
Optional condensate return piping from dispersion
unit; ¾" pipe thread (DN20) fitting at humidifier
Air vent height must be equal to
or greater than dimension “H”
(see table below)
Steam hose, pipe or tubing
H
Offset humidifier from floor
drain to prevent flash steam
from rising into the humidifier
Air vent tube
6" (150 mm)
minimum vent height
Install level
Installation