Page 34 • DRI-STEEM GTS Humidifier Installation, Operation, and Maintenance Manual
Special horizontal venting requirements
• Ensure that distances from the vent terminal to adjacent public
walkways, buildings, and openable windows and building
openings are consistent with the National Fuel Gas Code, ANSI
Z223.1, CAN/CGA B149 Installation Codes, National Gas
Safety Code (Installation & Use) Regulations (latest revision), or
governing codes.
• In areas accessible to the public, the vent terminal must be at
least 7' (2.1 m) above ground level to prevent burns from the hot
terminal surface.
• The vent terminal and air intake locations must be at sufficient
height above ground level to prevent blocking by expected
snowfall.
• Building materials must be protected from degradation by flue
gases.
• A minimum horizontal clearance of 4' (1.22 m) from electric
meters, gas meters, regulators, and relief equipment must be
maintained.
• Maximum equivalent length of vent pipe is 100' (30 m).
Minimum equivalent length of vent pipe is 10' (3 m). See power
venter installation manual for equivalent lengths of fittings.
• Vent box pressure must be –0.01" wc (–2.5 Pa). Set by adjusting
power venter and barometric damper, with all burners running
(see manufacturer's instructions included with power venter and
damper).
Ve r t i c a l a n d h o r i z o n t a l v e n t i n g
( c o n t i n u e d )
Table 34-2:
Recommended minimum vent sizes
Model
Minimum vent size
Vertical vent Horizontal vent
inches mm inches mm
GTS-100 5 130 5 130
GTS-200 5 130 5 130
GTS-300 7 180 5* 130
GTS-400 7 180 5* 130
GTS-500 8 205 8 205
GTS-600 8 205 8 205
GTS-700 10 255 8* 205
GTS-800 10 255 8* 205
Note:
* For best results, make transition to smaller vent
diameter as close to the power venter as possible.
Table 34-1:
Equipment required for horizontal
venting
Item
Field controls
model number
for GTS or
GTS-DI models
100, 200,
300, 400
Field controls
model number
for GTS or
GTS-DI models
500, 600, 700,
and 800
Power venter PVO-600 (5") PVE-1200 (8")
Barometric
damper
MG-1 (5") MG-1 (8")
Vent hood SWH-1-5 (5") SWH-8
Electrical
ratings
120 VAC
60 Hz
2.1 A
120 VAC
60 Hz
2.5 A
Note:
For European models, contact your distributor for
horizontal venting parts.
*
Figure 34-1:
GTS venting
Notes:
* Install a tee after the first elbow from the humidifier as shown. Use the open end of
this tee for the location of the barometric damper.
** Required distance between air intake and vent hood is defined by governing codes.
Refer to power venter manual for clearance requirements relative to combustion air
openings.
Power venter
Barometric draft control
installed in tee*
“x”
Air
intake
3½' (1.07 m)
min.
Vent hood
Recommended value
for “x” approximately
12" (305 mm)
OM-1209
Distance**
I m p o r t a n t : Seal the connection and all other vent
piping joints on the pressure side of the power venter.
Air intake
Installation