Page 22 DRI-STEEM GTS Humidifier Installation, Operation, and Maintenance Manual
S u p p l y w a t e r a n d d r a i n o v e r f l o w
c o n n e c t i o n s
Supply water and drain overflow connections
Regardless of the type of water used, the following general
instructions MUST be followed:
• Make union connections at the humidifier on the make-up water
supply and drain/overflow lines.
• Provide a shutoff valve in the supply water line to isolate the
humidifier from the water system while servicing.
• Shock arrester, provided by installer, is recommended to reduce
water hammer.
• A 1" (25 mm) opening is provided in the humidifier tank to
accommodate skim and/or overflow protection. (Note: Follow
governing code requirements regarding size of drain pipe.)
• Use insulating unions or bushings to make connections between
copper and other dissimilar metal fittings, such as galvanized
steel. These insulating fittings are required to minimize
electrolytic corrosion, which results from the direct connection of
dissimilar metals in a water system.
• Before beginning ignition sequence of the humidifier at a new
installation, make sure the humidifier tank is full of water and the
water is free to flow into the tank.
• If planning to use heated supply water, disconnect the water
supply line to the water tempering device at the fill manifold
and reconnect it to a cold water supply. This will ensure that the
water tempering device operates properly.
Table 22-1:
Connection sizes
Description
GTS-100
GTS-200
GTS-300
GTS-400
GTS-500
GTS-600
GTS-700
GTS-800
inches DN inches DN inches DN inches DN
Gas supply
½
(pipe thread)
15
1
(pipe thread)
25
1
(pipe thread)
25
(pipe thread)
32
Sealed combustion
piping (optional)
4 100 4 100 4 100 4 100
Flue vent 5 125 7 180 8 200 10 250
Water supply to fill valve
and tempering device*
3/8
(pipe thread)
10
3/8
(pipe thread)
10
3/8
(pipe thread)
10
3/8
(pipe thread)
10
Drain
(pipe thread)
40
(pipe thread)
40
(pipe thread)
40
(pipe thread)
40
Steam outlet
2
(pipe thread or
hose)
50
3
(flange)
80
4
(flange)
100
4
(flange)
100
Condensate return
(recommended)
¾
(pipe thread)
20
¾
(pipe thread)
20
¾
(pipe thread)
20
¾
(pipe thread)
20
Notes:
* In order to minimize DI/RO water use, disconnect factory piping to the water tempering device and pipe directly to tap water.
If planning to use heated supply water, disconnect the water line to the water tempering device at the fill manifold, and reconnect it to a cold water supply.
This will ensure that the water tempering device operates properly.
Installation