DRI-STEEM GTS Humidifier Installation, Operation, and Maintenance Manual • Page 19
W A R N I N G !
Installation must meet the requirements of governing codes or, in the
absence of governing codes, in accordance with the National Electrical
Code, ANSI/NFPA 70, or Canadian Electrical Code, CSA C22.1, or IEE
wiring regulations (BS7671). The electrical subpanel must have an
uninterrupted or unbroken ground to minimize personal injury if an
electrical fault should occur. This ground can consist of electrical wire
or conduit approved for electrical ground when installed in accordance
with existing electrical codes. Do not use gas piping as an electrical
ground.
• GTS humidifiers must be supplied with 120-volt AC, 60 Hz
(North American models) or 230-volt AC, 50 Hz (European
models) separately fused electrical service. The GTS humidifier is
equipped with a transformer to step down the voltage to 24 VAC
control voltage.
• When installed, the GTS humidifier must be electrically
grounded in accordance with governing codes or, in the absence
of governing codes, in accordance with the National Electrical
Code, ANSI/NFPA 70; or Canadian Electrical Code, CSA C22.1;
or IEE wiring regulations (BS7671).
In North America, the electrical conductors shall be Type MTW
(105 °C) AWG #14 (2.5 mm
2
) wire for 120 V line voltage , with
BLACK WIRE for HOT, WHITE WIRE for NEUTRAL, GREEN
AND YELLOW WIRE for GROUND. Units with outdoor
enclosure must use AWG #12 (4 mm
2
) for 120 V line voltage. Use
#18 gauge (1 mm
2
) for control wiring.
In Europe, the electrical conductors shall be Type MTW (105 °C)
2.5 mm
2
wire for line voltage (230V), with BLACK WIRE for
LINE, BLUE WIRE for NEUTRAL, GREEN AND YELLOW
WIRE for GROUND, and 2.5 mm
2
wire for control wiring.
• All electrical components and wiring must be protected from
mechanical damage and water. The control system requires an
earth ground for proper operation.
• The GTS humidifier is adjusted for correct performance. Only a
qualified gas appliance technician may alter throttle setting.
• Check the electric current characteristics and capacity
requirements against the nameplate. All wiring must be in
accordance with all governing codes and with the GTS wiring
diagrams located inside the control cabinet. See table on Page 8
for information on the various models.
• Refer to the Vapor-logic4 Installation and Operation Manual for
additional information on the controller furnished with this GTS
humidifier.
W i r i n g : E l e c t r i c a l c o n n e c t i o n s
W A R N I N G !
Do not connect aluminum wire between
disconnect switch and humidifier. Use
only copper wire. Failure to follow these
instructions could cause a fire, resulting in
severe bodily injury, death, or significant
property damage.