DRI-STEEM GTS Humidifier Installation, Operation, and Maintenance Manual Page 21
G T S p i p i n g , D I / R O w a t e r m o d e l s
Figure 21-1:
Field piping overview for GTS DI/RO water models
OM-1223
Notes:
Locate air gap only in spaces with adequate
temperature and air movement to absorb flash
steam; otherwise, condensation may form on nearby
surfaces. Refer to governing codes for drain pipe size
and maximum discharge water temperature.
Dashed lines indicate provided by installer.
Humidifier flue gases must be vented to the outside
atmosphere.
The water supply inlet is more than 1" (25 mm)
above the overflow port, eliminating the possibility of
backflow or siphoning from the tank. No additional
backflow prevention is required; however, governing
codes prevail.
Damage caused by chloride corrosion is not covered
by your DRI-STEEM warranty.
In order to minimize DI/RO water use, disconnect
factory piping to the water tempering device and pipe
directly to tap water.
See the previous page for recommended water supply
piping for standard water models.
Table 21-1:
Height required to overcome GTS-DI internal pressure (H)
GTS-DI model
number
H = Height required to overcome humidifier internal pressure
inches mm
100, 200 35 889
300, 400,
500, 600,
700, 800
41 1041
Water supply line; water
pressure range 25 psi to 80 psi
(172 kPa to 582 kPa); first 3'
(1 m) of supply line must be
rated for 212 °F (100 °C)
Flue connection
Gas inlet connection
1" (25 mm) air gap
1½" (DN40) drain piping must be
rated for 212 °F (100 °C)
Install level
Air vent tube height must
be equal to or greater than
dimension “H“ (see table below)
Steam hose, pipe or tubing
Install level
If water piping to humidifier is nonmetallic, we recommend
a 2" (50 mm) water seal in the supply line to isolate steam
during DI/RO water system maintenance.
Offset humidifier from floor
drain to prevent flash steam
from rising into the humidifier
H
Inlet strainer by installer
6" (150 mm)
minimum vent height
Open drain required. See first note below.
Air vent tube
Optional condensate return
piping from dispersion unit;
¾" pipe thread (DN20)
fitting at humidifier
Flue size per governing codes.
Do not reduce.
Installation