
P a g e 6 8 • D R I - S T E E M D e s i g n G u i d e
D R I - S T E E M D e s i g n G u i d e • P a g e 6 9
eliminates heat gain during the “off” humidification periods only
(see Figures 68-1 and 69-1). The jacketing steam valve should be
a two-position type, with a minimum Cv of 5, and set to the full-
open position prior to opening the modulating valve.
In Figure 68-1, all of the steam (for jacketing and humidification)
must pass through the jacket steam valve, and it must do so with
very little or no pressure drop across the valve, or maximum
capacity will be reduced. More importantly, with just one supply
source for jacket and humidification steam, the temperature of the
jacket steam may drop below the temperature required to eliminate
dripping. Therefore, the valve must be adequately sized. This is
not significant in a small capacity humidifier. However, in a large
capacity humidifier, the valve of the size required may be quite
expensive. Another option is to install two valves: one sized for
jacket steam and one sized for humidification steam.
Figure 69-1 shows a steam flow that has been divided into two
paths: a humidifying steam path (which passes through the
separator valve assembly) and a jacket steam path. When dividing
the steam path, install a temperature switch as shown in the
drawing to ensure that condensate is not present when the control
valve opens. Install a header trap, as shown, to collect condensation
when the jacket steam is off.
Figure 69-1:
Divided humidifying steam path
Note: Due to the pressure drop across the
valve, the steam pressure at the header
trap is minimal; therefore, you cannot
lift condensate or return condensate to a
pressurized return from this trap.
Jacketing steam on-off valve
Modulating control valve
Temperature switch
Header
trap
Drain
Komentáře k této Příručce