P a g e 6 0 • D R I - S T E E M D e s i g n G u i d e
D R I - S T E E M D e s i g n G u i d e • P a g e 6 1
Placing a dispersion assembly near an elbow (see Figure 60-1)
• Location A is the best choice. Better absorption occurs on the
downstream side of an elbow than on the upstream side.
• Location B is the second-best choice. Installing upstream of an
elbow can cause wetting at the turning vanes. In cases where it is
structurally impossible to avoid Location B, use a multiple tube
dispersion unit to ensure complete absorption. Also, since more
air flows along the outside of a turn, better absorption occurs if
the humidifier discharges proportionately more steam in that part
of the airstream.
• At both locations, discharging steam against or perpendicular to
the airstream gives slightly better mixing and absorption than
discharging with the airstream.
Figure 60-1:
Placing a dispersion assembly near an elbow
Duct
Airow
Mist can collect
on vanes
Less airow on
this side of elbow
3' to 5'
(1 m to 1.5 m)
8' to 12'
(2.4 m to 3.7 m)
Duct high limit humidistat
Airow
A
B