P a g e 4 2 D R I - S T E E M D e s i g n G u i d e
D R I - S T E E M D e s i g n G u i d e P a g e 4 3
Evaporative system components
1. Control cabinet
If a humidifier has a separate control cabinet, it can be mounted
either on the humidifier or remotely. Some humidifiers, like
the VAPORMIST, have control components integrated into the
humidifier cabinet. Systems using VAPOR-LOGIC control also
have a keypad (see Figure 42-2).
2. Water level control
Potable or softened water systems control water level
electronically using a three-rod probe. DI/RO water systems
control water levels using a float valve. Electric systems also have
a low-water cutoff float switch for heater protection (see detail
drawings on Pages 44 and 45).
3. Drain
DRI-STEEM offers a variety of drain types. Standard water
systems have electric drains that open for drain or drain/flush
cycles. Some standard water systems automatically drain when
there has been no call for humidity for 72 hours (“end-of-
season draining”). DI/RO water systems do not cycle through
regular drain or drain/flush cycles because DI/RO water does not
cause scale buildup. For this reason, most DI/RO systems have
a manual drain, although an electric drain can be ordered for
automated draining at end of season or when the humidifier is
idle for a defined period of time. Some systems allow the user to
adjust drain duration and interval either through a keypad or by
changing switches on the control board.
4. Water skimmer/overflow port
The water skimmer reduces minerals in the evaporating chamber
of standard water systems. Skimming occurs each time the
humidifier fills. The skim time duration is user adjustable on all
DRI-STEEM humidifiers by either using the keypad or setting
a switch on the control board. In DI/RO water models, the
skimmer port serves as an overflow port.
5. Heating elements/heat exchanger
Electric systems: Low-watt-density INCOLOY-sheathed
heating elements ensure operation for many seasons. Constant
expansion and contraction of heating elements sheds mineral
scale. In the unlikely event of heater failure, heating elements can
be replaced easily.
Heat exchanger systems: The heat exchanger transfers energy
from boiler steam (STS), hot water (LTS) or gas-fired burners
(GTS) to water in the evaporating chamber, generating steam.
Figure 42-1:
VAPORSTREAM electric system
1
2
3
4
5
8
7
8
9
Figure 42-2: