VAPORSTREAM INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
INSTALLATION
Sensor placement
Other factors affecting humidity control
Humidity control involves more than the
controller’s ability to control the system. Other
factors that play an important role in overall
system control are:
Size of humidification system relative to load
Overall system dynamics associated with
moisture migration time lags
Accuracy of humidistats and humidity
transmitters and their location
Dry bulb temperature accuracy in space or
duct
Velocities and airflow patterns in ducts and
space environments
Electrical noise or interference
mc_072011_1656
SENSOR LOCATION IS CRITICAL
Sensor location has a significant impact on humidifier performance. See the
recommendations below.
Note: DriSteem recommends that you do not interchange room and duct
humidity devices. Room humidity devices are calibrated with zero or
little airflow, whereas duct humidity devices require air passing across
them.
Recommended humidity control (transmitter/humidistat) locations:
A. Ideal. Ensures the best uniform mix of dry and moist air with stable
temperature control.
B. Acceptable, but room environment can affect controllability, such as when
sensor is too close to air grilles, registers, or heat radiation from room
lighting.
C. Acceptable. Provides uniform mixture of dry and moist air. If extended time lag exists between humidity generation
and sensing, extend sampling time.
D. Acceptable (behind wall or partition) for sampling entire room if sensor is near an air exhaust return outlet. Typical
placement for sampling a critical area.
E. Not acceptable. These locations might not represent actual overall conditions in the space.
F. Not acceptable. Do not place sensors near windows, door passageways, or areas of stagnant airflow.
Recommended safety (airflow and high limit) sensor location:
G. Best sensing location for high limit humidistat or humidity sensor and airflow proving switch.
mc_072011_1655
DC-1084
Outside air
Relief air
Return air
Air handling
unit
8' to 12'
(2.4 m to 3.7 m)
min.
Humidifier dispersion assembly
Turning vanes
Window
Doorway
Window
Point of vapor absorption
Vapor absorption has taken place
Airflow switch or differential pressure switch
(sail type recommended for VAV applications)
High limit humidistat or high limit transmitter (set at 90% RH maximum)
for VAV applications
Damper control
C
A
E
F
D
B
E
F
G
E
Wall or partition
mc_060508_0750
Temperature compensation option: Place a temperature compensation sensor on
the lower corner of the inside surface of double-pane window glass on north- or
northeast-facing window.
FIGURE 34-1: RECOMMENDED SENSOR LOCATIONS