VAPORSTREAM®Electric HumidifierInstallation, Operation, and Maintenance ManualREAD AND SAVE THESE INSTRUCTIONS
6VAPORSTREAM INSTALLATION, OPERATION, AND MAINTENANCE MANUALWeights and cabinet sizesSPECIFICATIONSTable 6-1:Vaporstream VLC weights and control cabin
7VAPORSTREAM INSTALLATION, OPERATION, AND MAINTENANCE MANUALWhen selecting a location for the humidifier, consider the following:• Easy access for mai
8VAPORSTREAM INSTALLATION, OPERATION, AND MAINTENANCE MANUALTo ensure that the water level control system works properly, the tank must be mounted lev
9VAPORSTREAM INSTALLATION, OPERATION, AND MAINTENANCE MANUALMounting:VLC-OM-006Optional set of four legs and hardwareINSTALLATIONSupport legs are not
10VAPORSTREAM INSTALLATION, OPERATION, AND MAINTENANCE MANUALFor overhead installations, install a drip pan to prevent possible water damage (see figur
11VAPORSTREAM INSTALLATION, OPERATION, AND MAINTENANCE MANUALDriSteem optional wall brackets (two required)A24.75" (629 mm)Table 11-1:Wall bracke
12VAPORSTREAM INSTALLATION, OPERATION, AND MAINTENANCE MANUALWeather coverINSTALLATION ISSUES SPECIFIC TO WEATHER COVER APPLICATIONS • Installation m
13VAPORSTREAM INSTALLATION, OPERATION, AND MAINTENANCE MANUALWeather coverThe Vaporstream Outdoor Enclosure is weather tight with access doors and sup
14VAPORSTREAM INSTALLATION, OPERATION, AND MAINTENANCE MANUALOutdoor Enclosure:INSTALLATIONNotes:1. The Outdoor Enclosure has two available steam dis
15VAPORSTREAM INSTALLATION, OPERATION, AND MAINTENANCE MANUALOutdoor Enclosure:INSTALLATIONBStandard steam outlet (exits enclosure here)Intake ventila
iiVAPORSTREAM INSTALLATION, OPERATION, AND MAINTENANCE MANUALWarnings and cautions WARNINGCAUTIONIndicates a hazardous situation that could result in
16VAPORSTREAM INSTALLATION, OPERATION, AND MAINTENANCE MANUALOutdoor Enclosure:INSTALLATIONTable 16-1:Vaporstream Outdoor Enclosure weightsVaporstream
17VAPORSTREAM INSTALLATION, OPERATION, AND MAINTENANCE MANUALOutdoor Enclosure:The Outdoor Enclosure option is used when DriSteem humidifiers are insta
18VAPORSTREAM INSTALLATION, OPERATION, AND MAINTENANCE MANUALOutdoor Enclosure:• Outdoor Enclosure must be level and located so there is enough clear
19VAPORSTREAM INSTALLATION, OPERATION, AND MAINTENANCE MANUALOutdoor Enclosure:• Outdoor Enclosure has two available steam distribution configurations
20VAPORSTREAM INSTALLATION, OPERATION, AND MAINTENANCE MANUAL• Keypad/display with standard 5' (1.5 m) cable ships mounted to subpanel in Outdoo
21VAPORSTREAM INSTALLATION, OPERATION, AND MAINTENANCE MANUALWhen power is applied to Outdoor Enclosure:• If ambient temperature in Outdoor Enclosure
22VAPORSTREAM INSTALLATION, OPERATION, AND MAINTENANCE MANUALINSTALLATIONPiping:Table 22-1:Heights required to overcome Vaporstream internal pressure
23VAPORSTREAM INSTALLATION, OPERATION, AND MAINTENANCE MANUALINSTALLATIONNotes:• Locate air gap only in spaces with adequate temperature and air move
24VAPORSTREAM INSTALLATION, OPERATION, AND MAINTENANCE MANUALThe drain line piped from the humidifier must be run to an approved sanitary waste or suit
25VAPORSTREAM INSTALLATION, OPERATION, AND MAINTENANCE MANUALDrainINSTALLATIONTAP/SOFTENED WATERThe drain connection to a tap/softened water humidifier
iiiVAPORSTREAM INSTALLATION, OPERATION, AND MAINTENANCE MANUALWarnings and cautions Warnings and Cautions WARNINGDisconnect electrical powerDisconnect
26VAPORSTREAM INSTALLATION, OPERATION, AND MAINTENANCE MANUALINSTALLATIONDrain VLC with RO/DI water option and manual drain has a pipe thread fitting o
27VAPORSTREAM INSTALLATION, OPERATION, AND MAINTENANCE MANUALVaporstream humidifiers have a 1" (25 mm) internal air gap to prevent back siphoning
28VAPORSTREAM INSTALLATION, OPERATION, AND MAINTENANCE MANUALINSTALLATIONRO/DI WATER SUPPLY PIPINGThe RO/DI-water Vaporstream humidifier controls water
29VAPORSTREAM INSTALLATION, OPERATION, AND MAINTENANCE MANUALWIRING DIAGRAM OVERVIEW• Ladder style wiring diagrams (located inside the control cabine
30VAPORSTREAM INSTALLATION, OPERATION, AND MAINTENANCE MANUALINSTALLATIONWiring:Incoming power conduit penetration, hole size determined by humidifier
31VAPORSTREAM INSTALLATION, OPERATION, AND MAINTENANCE MANUALTable 31-2: European breaker requirementsI max. A Breaker size0 - 8.0 108.1 - 10.4 1310.
32VAPORSTREAM INSTALLATION, OPERATION, AND MAINTENANCE MANUALINSTALLATIONElectrical noise can produce undesirable effects on electronic control circui
33VAPORSTREAM INSTALLATION, OPERATION, AND MAINTENANCE MANUALWiring:CONTROL WIRINGThe following wiring methods for external low voltage control wiring
34VAPORSTREAM INSTALLATION, OPERATION, AND MAINTENANCE MANUALINSTALLATIONSensor placementOther factors affecting humidity controlHumidity control invo
35VAPORSTREAM INSTALLATION, OPERATION, AND MAINTENANCE MANUALDispersion:Important:Failure to follow the recommendations in this section can result in
ivVAPORSTREAM INSTALLATION, OPERATION, AND MAINTENANCE MANUALTable of contentsATTENTION INSTALLERRead this manual before installing. Leave manual with
36VAPORSTREAM INSTALLATION, OPERATION, AND MAINTENANCE MANUALINSTALLATIONThe steam outlet on the humidifier is sized to the output of the humidifier. DO
37VAPORSTREAM INSTALLATION, OPERATION, AND MAINTENANCE MANUALTable 37-1:Maximum steam carrying capacity and length of interconnecting steam hose or tu
38VAPORSTREAM INSTALLATION, OPERATION, AND MAINTENANCE MANUALINSTALLATIONmc_022510_16026" long (152 mm) hose cuffHose clampsTubingSteam outlet co
39VAPORSTREAM INSTALLATION, OPERATION, AND MAINTENANCE MANUALSteam outlet connectionsmc_022510_1603DC-1141Steam outlet connection (flange)Directional a
40VAPORSTREAM INSTALLATION, OPERATION, AND MAINTENANCE MANUALNotes:• Locate air gap only in spaces with adequate temperature and air movement to abso
41VAPORSTREAM INSTALLATION, OPERATION, AND MAINTENANCE MANUALDISPERSION TUBE MOUNTING• Orient dispersion tube(s) so that tubelets (steam orifices) poi
42VAPORSTREAM INSTALLATION, OPERATION, AND MAINTENANCE MANUALBB90° long sweep or two 45° elbowsVaporstream humidifierSecure and seal duct escutcheon pl
43VAPORSTREAM INSTALLATION, OPERATION, AND MAINTENANCE MANUALDispersion tube plateCondensate drain plate90° long sweep or two 45° elbowsVaporstream hu
44VAPORSTREAM INSTALLATION, OPERATION, AND MAINTENANCE MANUALOM-351bMounting bracketMovable escutcheon plate. Plate can be mounted within limits of 2.
45VAPORSTREAM INSTALLATION, OPERATION, AND MAINTENANCE MANUALDuctVaporstream humidifier½" (DN15) O.D. condensate drain tube, pitch ¼"/ft (2%)
1VAPORSTREAM INSTALLATION, OPERATION, AND MAINTENANCE MANUALTable of contentsKeypad/display and troubleshootingThe Vapor-logic version 5 Installation
46VAPORSTREAM INSTALLATION, OPERATION, AND MAINTENANCE MANUALRapid-sorbCAUTIONOperate Rapid-sorb within rated steam capacityExcessive steam flow to the
47VAPORSTREAM INSTALLATION, OPERATION, AND MAINTENANCE MANUALTable 47-3: Pitch of interconnecting piping, dispersion tubes, and headers for Rapid-sorb
48VAPORSTREAM INSTALLATION, OPERATION, AND MAINTENANCE MANUALVaporstream humidifier6" (152 mm) minimumDuct 5" (127 mm) AirflowDispersion tube9
49VAPORSTREAM INSTALLATION, OPERATION, AND MAINTENANCE MANUALRapid-sorb5. Before tightening the L-bracket bolts to the dispersion tubes:• For 1½&quo
50VAPORSTREAM INSTALLATION, OPERATION, AND MAINTENANCE MANUALDC-10516" (152 mm) minimumPoint tubelets (steam orifices) perpendicular to airflow Duc
51VAPORSTREAM INSTALLATION, OPERATION, AND MAINTENANCE MANUALRapid-sorbNote:See Page 52 for steam supply and condensate drain line connection instruct
52VAPORSTREAM INSTALLATION, OPERATION, AND MAINTENANCE MANUALRapid-sorbSTEAM SUPPLY CONNECTIONS TO RAPID-SORB HEADERConnect the steam supply interconn
53VAPORSTREAM INSTALLATION, OPERATION, AND MAINTENANCE MANUALSDU-I and SDU-ECHOOSING A LOCATION FOR SDU-I AND SDU-E• When used with a Vaporstream, th
54VAPORSTREAM INSTALLATION, OPERATION, AND MAINTENANCE MANUALControl board in Vaporstream control cabinetVLC-OM-032SDU-I cabinet with shroud removedS
55VAPORSTREAM INSTALLATION, OPERATION, AND MAINTENANCE MANUALSDU-EInstall SDU-E frame plumb and levelUnionElbow1" (25 mm) air gapDispersion box¾&
2VAPORSTREAM INSTALLATION, OPERATION, AND MAINTENANCE MANUALFIGURE 2-1: VAPORSTREAM SYSTEM EXAMPLE, TAP/SOFTENED WATERProduct overviewTAP/SOFTENED WAT
56VAPORSTREAM INSTALLATION, OPERATION, AND MAINTENANCE MANUALTable 56-1:SDU-E minimum nonwetting distanceskWMaximum steam capacity40% RH @ 70 °F (21 °
57VAPORSTREAM INSTALLATION, OPERATION, AND MAINTENANCE MANUALTable 58-1 lists the Area-type steam minimum rise, spread, and throw nonwetting dimension
58VAPORSTREAM INSTALLATION, OPERATION, AND MAINTENANCE MANUALTable 58-1: Area-type (evaporative steam) minimum distances for rise, spread, and throw*M
59VAPORSTREAM INSTALLATION, OPERATION, AND MAINTENANCE MANUALAfter the system is installed and connected properly: 1. Verify that the Vaporstream hum
60VAPORSTREAM INSTALLATION, OPERATION, AND MAINTENANCE MANUALOPERATIONIf an item in the Start-up checklist below does not apply to your system, skip t
61VAPORSTREAM INSTALLATION, OPERATION, AND MAINTENANCE MANUALTap/softened water:MAINTENANCE WARNINGElectric shock hazardContact with energized circuit
62VAPORSTREAM INSTALLATION, OPERATION, AND MAINTENANCE MANUALTap/softened water:MAINTENANCECAUTIONHot discharge waterDischarge water can be as hot as
63VAPORSTREAM INSTALLATION, OPERATION, AND MAINTENANCE MANUALINSPECTION AND MAINTENANCE 1. Annually (also recommended when maintenance is performed)•
64VAPORSTREAM INSTALLATION, OPERATION, AND MAINTENANCE MANUALTap/softened water:MAINTENANCEHumidifier De-scaling SolutionScale buildup on humidifier he
65VAPORSTREAM INSTALLATION, OPERATION, AND MAINTENANCE MANUALRO/DI water option:MAINTENANCE WARNINGElectric shock hazardContact with energized circuit
3VAPORSTREAM INSTALLATION, OPERATION, AND MAINTENANCE MANUALProduct overview OM-1000Cover fastenerCoverFloat valveOverflowLow-water cutoffDrain valveHu
66VAPORSTREAM INSTALLATION, OPERATION, AND MAINTENANCE MANUALRO/DI water option:Note:When replacing the cleanout plate, tighten nuts to a torque measu
67VAPORSTREAM INSTALLATION, OPERATION, AND MAINTENANCE MANUALOutdoor EnclosureAccess to the humidifier side cleanout plate is through the Outdoor Enclo
68VAPORSTREAM INSTALLATION, OPERATION, AND MAINTENANCE MANUALNote: Components may be in a different location or have a different orientation than sho
69VAPORSTREAM INSTALLATION, OPERATION, AND MAINTENANCE MANUALTable 69-1:Tank replacement parts listNo. Description Models used Part no.1 Tank All *2 C
70VAPORSTREAM INSTALLATION, OPERATION, AND MAINTENANCE MANUALVLC-OM-035aControl cabinetREPLACEMENT PARTSNote: Components may be in a different locati
71VAPORSTREAM INSTALLATION, OPERATION, AND MAINTENANCE MANUALTable 71-1:North American control cabinet replacement parts No. Description Models that u
72VAPORSTREAM INSTALLATION, OPERATION, AND MAINTENANCE MANUALSDU-IREPLACEMENT PARTSOM-1504Table 72-1:SDU-I replacement partsNo. Description Qty. Part
73VAPORSTREAM INSTALLATION, OPERATION, AND MAINTENANCE MANUALSDU-EREPLACEMENT PARTSOM-1503Table 73-1:SDU-E replacement partsNo. Description Qty. Part
74VAPORSTREAM INSTALLATION, OPERATION, AND MAINTENANCE MANUALOutdoor EnclosureREPLACEMENT PARTSOM-953Table 74-1: Outdoor Enclosure replacement partsN
75VAPORSTREAM INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
4VAPORSTREAM INSTALLATION, OPERATION, AND MAINTENANCE MANUALModels, capacities, and electrical specificationsSPECIFICATIONSTable 4-1:Vaporstream VLC ca
Form No. VLC-IOM-1013Part No. 890000-801 Rev HTwo-year Limited WarrantyDriSteem Corporation (“DriSteem”) warrants to the original user that its produc
5VAPORSTREAM INSTALLATION, OPERATION, AND MAINTENANCE MANUALSPECIFICATIONSVLC-OM-039CB’C'ABA’Table 5-2:Vaporstream VLC dimensions, tap/softened w