Page 14 DRI-STEEM Vapor-logic3 to Vapor-logic4 Adaptor Board Installation Manual
Electric humidifiers:
Safety circuit wiring
Figure 14-1:
Leaving safety circuit wired in series with one alarm
•  CRUV without door interlock,
•  Vapormist
•  Humidi-tech
The following procedure leaves the safety circuit (door interlock and
low water) wired in series with one alarm:
1. Verify that jumpers shown in Figure 14-1 are in place.
2. Land wire 802 at terminal P3-3 on Vapor-logic4 adaptor board (see
Figure 14-1).
3. Humidi-tech only: Clamp ferrite core around drain valve wiring.
Proceed to “Start-up and validation” on Page 19.