P a g e 2 2 • D R I - S T E E M V a p o r s t r e a m h u m i d i f i e r
Va p o r s t r e a m M o d e l V L C p i p i n g
Figure 22-1:
Field piping overview for Vaporstream Model VLC (standard water models)
Table 22-1:
Heights required to overcome Vaporstream internal pressure
(H1, H2)
Unit output
Water seal height
(H1)
Air vent height
(H2)
kW lbs/hr kg/h inches mm inches mm
≤ 48 ≤ 138 ≤ 62 12 305 22.5 572
49-64 139–183 63–83 15 381 27.5 699
> 64 > 183 > 83 18 457 30.5 775
Figure 22-1 notes:
• Locate air gap only in spaces with adequate temperature and air movement to absorb flash steam; otherwise, condensation may form on nearby surfaces.
Refer to governing codes for drain pipe size and maximum discharge water temperature.
• Offset humidifier from floor drain to prevent flash steam from rising into the humidifier.
• Dashed lines indicate provided by installer.
• The water supply inlet is more than 1" (25 mm) above the skim/overflow port, eliminating the possibility of backflow or siphoning from the tank. No
additional backflow prevention is required; however, governing codes prevail.
• Damage caused by chloride corrosion is not covered by your DRI-STEEM warranty.
• See the next page for recommended water supply piping for Model VLDI (DI/RO water model).
VLC-OM-010
Figure 22-2:
VLC Models 2-1 through 5-1 piping
OM-4005
Drain piping
Drain valve
Fill valve
Overflow port
Install level
Install level
¾" (DN20) minimum
condensate drain piping
rated for 212 °F (100 °C)
Air vent height
must be equal to
or greater than
dimension H2
(see table below).
Air vent
tube
Optional condensate
return piping from
dispersion unit
Steam outlet
Shock arrester recommended to reduce water hammer
¾" (DN20) min. drain, skim, and overflow
piping rated for 212 °F (100 °C)
Manual or electric drain valve
If run is over 10' (3 m), increase
pipe to 1¼" (DN32)
Flow line of drain piping after the water
seal must be below the drain valve to
ensure that humidifier drains
correctly
1" (25 mm) air gap
Drain piping
flow line
¾" pipe thread
(DN20) dispersion
unit condensate
return inlet
Pitch 1/8"/ft (1%)
6"
(150 mm)
minimum
Open drain required. See first note below.
Water supply line; water pressure range 25 psi to 80 psi (172 kPa to
552 kPa); water conductivity minimum 100 µS/cm. If water piping
to humidifier is nonmetallic, we recommend that the first 3' (1 m)
of water supply piping from the humidifier be metallic with a 2"
(50 mm) water seal or loop in the supply line to isolate steam from
nonmetallic supply piping.